TM 5-4310-372-14
FUEL SYSTEM MAINTENANCE - continued
4-19. CLEANING, INSPECTION AND REPAIR - continued
NO.
ITEM(S)
ACTION
ITEM I.D.
5.
Cap and Gasket
(cent)
WARNING
Drycleaning solvent P-D-680, used to clean parts, is potentially dangerous to
personnel and property. Avoid repeated and prolonged skin contact by wearing
rubber or solvent impermeable gloves when handling the solvent or material wet
with drycleaning solvent. Wash hands immediately after exposure with soap and
water and use a Ianolin based skin cream to prevent skin drying. Do not use near
open flame or excessive heat. Flash point of solvent is 100°F (38°C). Ensure that
ventilation is adequate to reduce solvent vapor concentrations below acceptable
threshold limit values.
c.
Clean dirt from cap using
soft rag and solvent,
6.
Inlet Fuel Screen
a.
Inspect for damage
b. Replace if damaged.
c.
Clean by reverse
flushing with water.
WARNING
When using compressed air for blowing, air hose pressure must not exceed 30
psi (2.11 kg/sq.cm.), and individuals must wear eye protective equipment.
7.
Vent
8.
Level Indicator
d.
a.
b.
c.
a.
b.
c.
Blow off water with
compressed air.
inspect threads for damage.
Replace if damaged.
Clean by blowing out
with compressed air.
Inspect for damage.
Check for free movement
of float and correspond-
ing level indication.
Replace if damaged.
10
11
12
4-24
Change 3