TM 5-4310-373-14
3-4
TROUBLESHOOTING PROCEDURES.
This manual cannot list all malfunctions that may occur,
nor all tests or inspections and corrective actions. If a mal-
function is not listed or is not corrected by listed corrective
The table lists the common malfunctions which you may
find during the operation or maintenance of the air com-
actions, notify organizational maintenance.
pressor or its components. You should perform the tests/
inspections and corrective actions in the order listed.
Table 3-1. Troubleshooting
Malfunction
Test or Inspection
Corrective Action
1. ELECTRIC MOTOR WON'T START.
Step 1. See if main power switch is on.
Turn on main power.
Step 2. Check if overload condition has opened the overload relay.
Push RESET button on starter box.
Figure 3-2. Reset button operation
3-2