TM 5-4220-227-14
6-12.
Condensing Unit Hermetic (Cont).
(5)
Remove insulation and separate probe (9) from line (7).
(6)
Remove condensing unit (10) from module base (11).
(7)
Install condensing unit (10) on module base (11).
(8)
Install line (7) on probe (9) and wrap with insulation.
(9)
Install fitting (8) and tighten fitting (8) and nut (6).
(10)
Install six bolts (5), washers (4) and nuts (3).
(11)
Install cover (2) and secure with 14 screws (1).
b.
Repair.
(1)
Replace fan motor. (figure 6-20).
(a)
Remove four bolts (1) and remove fan guard (2).
(b)
Remove four blind head screws (3) and remove fan motor (4).
(c)
Remove fan blade (5) from fan motor (4).
(d)
Remove four screws (6) and bracket (7) from fan motor (4).
(e)
Remove two screws (8) and remove conduit bracket (9).
(f)
Loosen screw (10) on connector (11) and remove connector.
(g)
Remove two anti-short bushings (12) and flex conduit (13).
(h)
Install two anti-short bushings (12) and flex conduit (13).
(i)
Install connector (11) on conduit (13) and tighten screw (10).
(j)
Install conduit bracket (9) and secure with two screws (8).
(k)
Install bracket (7) on fan motor (4) and secure with four screws (6).
(/)
Install fan blade (5) on fan motor (4).
(m)
Install fan motor (4) and secure with four blind-head screws (3).
(n)
Install fan guard (2) and secure with four bolts (1).
6-44