TM 55-1905-223-24-8
Table 2-2. Troubleshooting - CONT
Malfunction
Test or Inspection
Corrective Action
4.
STEP 1. Check for excessive system leakage.
Secure all fittings and connections.
STEP 2. Check for inadequate lubrication.
STEP 3. Check for inadequate ventilation.
Remove any ventilation obstructions.
STEP 4. Check for wrong pulley rotation/installation.
Correct rotation.
5.
Excessive belt wear.
alignment.
STEP 2. Check belt tension.
STEP 3. Check to see if pulley is wobbling.
STEP 4. Check for damaged or rough pulley groove.
6.
Excessive current draw.
STEP 1. Check for loose electrical connections.
Secure all connections.
STEP 2. Check for low input voltage (less than 216 volts).
Troubleshoot switchboard and distribution circuits
(TM 55-1905-223-24-18).
STEP 3. Check for low oil pressure.
Check oil level gauge and add oil if needed (Table 2-1, PMCS, Item 1).
2-7