TM 5-4310-368-14
Section III. OPERATION UNDER USUAL CONDITIONS
2-3. ASSEMBLY AND PREPARATION FOR USE
No unpackaging is required. The only necessary installation is the air service hose (coiled on the inside of the
instrument panel access door) which is fitted to the hose disconnect fitting beside the instrument panel. See
depreservation instructions delivered with each unit.
2-4. INITIAL ADJUSTMENTS AND DAILY CHECKS
a.
Perform the B (before operation) checks and services from Table 2-2.
b.
Open all doors if operating in weather above freezing (32 ). These include instrument panel access door,
F
sliding side cooling door. Between 32 and 0 , close the front and rear cooling air exhaust doors. Below
F
F
0 to -50 , close all doors except the instrument panel access door.
F
F
c.
Push the clutch operating lever in to disengage the clutch.
d.
e.
Pull out spring tab and bend it so that the end fits in the slot in the engine oil pressure switch (Fig. 2-3).
Figure 2-2. Magneto Ground Switch
2-10